Active harmonic filters: Improved power quality and reduced harmonics
.

An increasing number of loads are non-linear, introducing harmonics into the power grid and thus significantly impairing the power quality. EPCOS PQSine is an active harmonic filter that effectively reduces the unwanted harmonics.

Linear loads have become a rarity in industrial plants, office buildings, data centers or even private households. Non-linear loads, by contrast, have become increasingly common: frequency converters in drive systems, the large numbers of switch-mode power supplies used in IT and communications equipment, and also more and more in household electronics. Even lighting technology employs mainly non-linear power supplies (Figure 1).
The non-linear current draw results in harmonics that cause distortion in the sinusoidal voltage, which in turn can cause interference for other loads. Harmonics are integer multiples of the basic frequency, i.e. of the line frequency of 50 Hz or 60 Hz. The harmonics have varying amplitudes and can extend into the upper kHz range.

Harmonic pollution has a series of negative effects on power quality, including:
• Problems for other loads due to the poor grid power quality.
• Additional current load on the neutral conductor, as the harmonic currents contained of the 3rd, 9th, 15th, and 21st order etc. are accumulative and lead to inadmissibly high currents.
• Phase-asymmetry (specifically when operating single-phase switch-mode power supplies) which additionally promotes the generation of harmonics.

In addition, harmonics transmitted via data or power lines can severely impair the function of sensitive devices or even destroy them. Typical examples include process controllers in factories or servers in data centers, where data corrupted by harmonics can cause enormous consequential damage.

Attempts are often made to eliminate harmonics directly at the load using passive components. This however necessitates a well-tuned resonant circuit for every harmonic frequency comprising capacitors and inductors. Such a solution, however, is only practicable if there is a limited spectrum of harmonics.

Advertising

EPR Android App Banner

Active harmonic filters compensate harmonics
With the EPCOS PQSine series, TDK now offers an elegant and full automatic solution for many of the problems caused by harmonics and phase shifts. PQSine is connected to the grid in parallel with the load that is causing the harmonics. The heart of the new active harmonic filters is a controller based on a 32-bit digital signal processor (DSP) with a sampling rate of 48 kHz. With a response time of just 21 µs, PQSine offers class-leading performance. Its new selective drive control (SDC) algorithm is faster than conventional algorithms based on fast Fourier transform (FFT) analysis. Using the data determined in real time, PQSine feeds a compensation current into the grid, which cancels the non-linearity of the load current (Figure 2).

The PQSine series is designed for 3-phase grids with or without neutral conductors with voltages of between 200 V AC and 480 V AC at 50/60 Hz. PQSine enables harmonics of up to the 50th order (2500 Hz/3000 Hz) to be detected and filtered. The new filters can be cascaded in 60 A steps up to a maximum compensation current of 600 A in a single filter system.

High flexibility due to modular structure
The modular structure of PQSine offers enormous benefits. The 60 A modules can swiftly be replaced. In addition, a standard control cabinet with 180 A filter performance can quickly be expanded with one or two 60 A modules, for example, to a total output of up to 300 A (5 modules). To do this the modules are simply inserted into the cabinet with a busbar that is fundamentally designed for currents up to 300 A (Figure 3). Contacting requires neither screwing nor drilling, as both the power connections and control cables feature plug-in connectors.

Unlike conventional power factor correction, which can only compensate inductive loads, PQSine is also able to compensate capacitive reactive power components. In addition to their outstanding filtering capabilities, PQSine active harmonic filters also ensure balancing of the loads to all three phases. Moreover, neutral conductor currents are also compensated when using 4-wire devices. Optimum reliability is ensured by means of a series of self-monitoring systems. The most important of these are: overload protection, shutdown on overtemperature, protection against overvoltage or undervoltage and fan monitoring. A choice of 7-inch and 12.1-inch TFT colour touchscreens is available for user-friendly input and reading of the data. PQSine offers a number of standard interfaces for control, programming, or diagnostics purposes: Ethercat 100 Mbit/s, USB, Active Sensor Bus and Display Bus.
The three-level output topology of PQSine (above) produces a better approximation of the output current to a sinusoidal waveform (below). In addition, it reduces losses.

Low loss output topology
Many active filters employ two-level IGBT bridges at the output, in other words, an output topology that is comparable with that of 6-pulse frequency converters. PQSine, on the other hand, employs a three-level topology with a total of 12 IGBTs (4 IGBTs per phase conductor). This achieves a considerably better approximation to a sinusoidal wave of the output signal than is possible with two-stage systems (Figure 4). Switching losses are also considerably reduced because each IGBT only has to switch half of the operating voltage in the three-level topology.

Cookie Consent

We use cookies to personalize your experience. By continuing to visit this website you agree to our Terms & Conditions, Privacy Policy and Cookie Policy.

Android App
Android App

Events

RenewX
RenewX
Wiretech 2025
Wiretech 2025
Power Gen
Power Gen
World Utilities Congress
World Utilities Congress
India Green Energy Expo
India Green Energy Expo

Our Sponsors

Wika
Wika
Ramelex
Ramelex
Rayzon Solar Pvt Ltd
Rayzon Solar Pvt Ltd
Akansha
Akansha
Andritz Hydro Pvt Ltd
Andritz Hydro Pvt Ltd
Vyoma Switchgear
Vyoma Switchgear
Skipper Limited
Skipper Limited
Joint Well
Joint Well
Kp Group
Kp Group
Credence Solar
Credence Solar
Grew Solar
Grew Solar
Nirmal
Nirmal
Meco Instruments Pvt Ltd
Meco Instruments Pvt Ltd
Novasys
Novasys
HPL Electric Power
HPL Electric Power
Sun Bond
Sun Bond
Supremesolar
Supremesolar
Vsole Solar
Vsole Solar
Elev8 Lift
Elev8 Lift
Power trac Group
Power trac Group
Omicron
Omicron
Ganz Electric
Ganz Electric
Eplan
Eplan
Aeron Composite Pvt Ltd
Aeron Composite Pvt Ltd
Eaton
Eaton
A-1 ELECTRICALS
A-1 ELECTRICALS
Ashone Technologies
Ashone Technologies
MENNEKES Electric India
MENNEKES Electric India
PRAMA HIKVISION INDIA
PRAMA HIKVISION INDIA
Motwane Manufacturing
Motwane Manufacturing
Sun Cables
Sun Cables