IoTx prevented transformer shutdown and probable explosion saving huge revenue loss

By March 3, 2020 5:39 pm IST

IoTx prevented transformer shutdown and probable explosion saving huge revenue loss
.

Transformer oil is essential in the overall functioning of a transformer. Moreover, an inadequate level or leakage of transformer oil could lead to a major mishap that can affect assets as well as human safety. This became a reality in one of The Motwane Manufacturing Company Pvt. Ltd.’s customer’s case with a 315 kVA transformer installed at their manufacturing facility. Motwane’s IoTx, a digital transformer monitoring system, helped them identify an oil leakage in the conservator that might have led to the transformer shutdown and probable explosion affecting human safety and huge revenue loss, had it gone undetected. IoTx monitors critical transformer parameters on a real-time basis and gives alarm/notification in case of any anomalies.

This 315 kVA transformer has an IoTx installed. In the absence of IoTx, it could have been impossible to detect an oil leakage, unless a physical inspection was carried out. It would also have been difficult to detect the exact location of leakage by correlating loading conditions and oil level.

Root cause and issue identified by IoTx (digital transformer monitoring unit): Oil leakage from transformer
Earlier when this issue was raised on 4th December 2019, the quantity of oil filled in the conservator was recorded at 60 percent of the conservator’s total oil level.
⦁ First issue of low oil level in the conservator was observed on 11th December 2019 by IoTx.
⦁ Since then, IoTx monitored the oil level in conservator every 5 minutes, until it was refilled and leakage issue was resolved on 23rd January 2020.

Transformer oil level daily instance report

The above diagram shows each hour of oil level status for January.

The oil level was below the set limit, but due to contraction and expansion of the oil, this level used to rise above the set limit for a specific amount of time, majorly in the daytime when the loading on the transformer was more and the ambient temperature was high.
⦁ It was found that the oil level was below the set level every day from 9 PM to 1 PM; this might be because of less loading on the transformer and low ambient temperature.
⦁ It was also found that the oil level was above the set level every day from 1 PM to 9 PM; this might be because of more loading on the transformer and high ambient temperature.

By virtue of streaming data available through IoTx, Motwane plotted a graph of the gradient of oil temperature rise with respect to percent loading. The purpose of the below graph is to establish a correlation between the loading of the transformer and the rise in oil temperature.

Advertising

EPR Android App Banner

   Transformer oil temperature gradient report for November 2019

   Transformer oil temperature gradient report for January 2020

The above two graphs depicted that the gradient of oil temperature rise with respect to percent loading was nearly about the same, i.e., 42℃ for 41-50 percent. This signified that the oil level in the transformer tank was good. Hence, it was confirmed that the oil leakage issue was only at the conservator of the transformer.

The transformer was saved from the following possible anomalies:
⦁ The oil level in the transformer tank could have decreased, which might have ultimately resulted in heating the transformer winding and transformer oil.
⦁ Air bubbles and impurities in oil could have increased, which might have decreased the oil quality and an insulation breakdown.
⦁ The transformer winding might have burned out due to the high winding temperature, which could have been a huge monitory loss.
⦁ Also, downtime could lead to revenue loss.

The transformer and revenue loss was ultimately saved by the virtue of IoTx
⦁ Beyond repair: Transformer price/replacement cost (approximate): ₹2,50,000-₹2,80,000
⦁ Repairing cost/winding replacement/oil replacement cost (approximate): ₹80,000-₹1,20,000
⦁ Saved 30 percent of transformer oil
⦁ Revenue loss due to transformer failure: Per day production loss (varies case to case basis)

Source:- https://bit.ly/2Ikh1S2

Cookie Consent

We use cookies to personalize your experience. By continuing to visit this website you agree to our Terms & Conditions, Privacy Policy and Cookie Policy.

Android App
Android App

Events

RenewX
RenewX
Wiretech 2025
Wiretech 2025
Power Gen
Power Gen
World Utilities Congress
World Utilities Congress
India Green Energy Expo
India Green Energy Expo

Our Sponsors

Wika
Wika
Ramelex
Ramelex
Rayzon Solar Pvt Ltd
Rayzon Solar Pvt Ltd
Akansha
Akansha
Andritz Hydro Pvt Ltd
Andritz Hydro Pvt Ltd
Vyoma Switchgear
Vyoma Switchgear
Skipper Limited
Skipper Limited
Joint Well
Joint Well
Kp Group
Kp Group
Credence Solar
Credence Solar
Grew Solar
Grew Solar
Nirmal
Nirmal
Meco Instruments Pvt Ltd
Meco Instruments Pvt Ltd
Novasys
Novasys
HPL Electric Power
HPL Electric Power
Sun Bond
Sun Bond
Supremesolar
Supremesolar
Vsole Solar
Vsole Solar
Elev8 Lift
Elev8 Lift
Power trac Group
Power trac Group
Omicron
Omicron
Ganz Electric
Ganz Electric
Eplan
Eplan
Aeron Composite Pvt Ltd
Aeron Composite Pvt Ltd
Eaton
Eaton
A-1 ELECTRICALS
A-1 ELECTRICALS
Ashone Technologies
Ashone Technologies
MENNEKES Electric India
MENNEKES Electric India
PRAMA HIKVISION INDIA
PRAMA HIKVISION INDIA
Motwane Manufacturing
Motwane Manufacturing
Sun Cables
Sun Cables