SAS fully under control
By EPR Magazine Editorial March 7, 2019 4:36 pm IST
By EPR Magazine Editorial March 7, 2019 4:36 pm IST
During the commissioning of substation automation systems (SAS) with protection automation and control (PAC), traditionally the focus of testing is on the protection system and its settings. Protection testing uses established methods, such as parameter testing per IED, or new approaches like system-based testing. Standardisation and proper testing tools dramatically increase the efficiency and reliability of protection testing.
When looking at the time spent during commissioning, testing the automation and communication system nowadays consumes even more time than testing the protection. Automation systems have become increasingly complex and the efforts for testing communication and the proper operation of all signals transmitted to supervisory control and data acquisition (SCADA) systems have grown dramatically.
The way out
A new and innovative approach, implemented in StationScout, offers a way out of this dilemma in all phases of the life cycle of modern SAS. By utilising the capabilities of the IEC 61850 engineering process and the data available in substation configuration description (SCD) files, it is possible to introduce new and more efficient methods for factory acceptance testing (FAT) and site acceptance testing (SAT). The approach identifies potential signals to be tested in the SCD file. Communication links and the IEC 61850 services employed are recognised, documented and can be used for generating test plans. These test templates can be created during the specification phase, adapted for FAT and subsequently reused during SAT.
This unique testing solution consists of software and hardware. While the software offers a toolbox for the different tasks, the use of a dedicated test set (MBX1) instead of just another PC software opens up a number of advantages to the test engineer:
Cyber security is very important when connecting a universal software based test system, such as a laptop, directly to a SAS. That’s why OMICRON has implemented a firewall system to the MBX1 that separates the testing system from the critical environment.
System under test
The entire SAS is visualised using all the information available in the SCD file. This also covers the information in the substation section (voltage level, bay, etc.). The current standard defines possibilities to model the elements of single line diagrams while the standard presently under development, IEC 61850-6-2, will extend this feature. Current SCD files do not, in most cases, contain this information. Therefore, the proposal is to work with ‘zero line’ to visualise the assets. Zero line means grouping by voltage level and arranging the bays and corresponding assets. The navigation in huge SAS can then be done as it is in map systems. Clicking ‘Go-live’ visualises the existing status.
Tracing signals
Within a SAS, the messages are transferred from their source to all receivers. If any error occurs during this communication, the commissioning engineers need to follow the signal on its way through the SAS. Finding such errors was very time consuming in copper wired networks, with IEC 61850 this becomes almost impossible to do manually. StationScout visualises all links and allows engineers to view how signals propagate through the SAS. To reduce complexity, filters focus the display on the relevant elements. This includes tracing signals communicated as GOOSE as well as reports and makes troubleshooting communication problems straightforward.
Authored by
Thomas Schossig,
Product Manager-Business Development Power Utility Communication,
OMICRON electronics